5.2.1.13. HB alarm threshold percentage
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
Hb.P
Alarms HB Alarm
R/W
% 90.0
HB alarm threshold percentage of the current read in HB calibration.
Recommended values for the number of equal parallel loads controlled by a single SSR:
min...max: 0.0 ...100.0%
5.2.1.14. Current reading in HB calibration
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
Hb.tA
Alarms HB Alarm
R/W
A 0.0
Current value read during the HB calibration procedure.
5.2.1.15. Voltage reading in HB calibration
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
Hb.tV
Alarms HB Alarm
R/W
A 0.0
Voltage value read during the HB calibration procedure.
5.2.1.16. Power read in HB calibration
Acronym App / GF_eXpress menu Attribute Retentive U.M. Default
Description
Hb.Pw
Alarms HB Alarm
R/W
A 0.0
Power value read during the HB calibration procedure.
no. loads Recommended percentage Hb.P
1 load 50.0%
2 loads 75.0%
3 loads 83.0%
4 loads 87.0%
5 loads 90.0%
6 loads 92.0%
7 loads 93.0%
8 loads 94.0%