Installation Planning
8 Installation Guidelines for Spark-Ignited Stationary Emergency Generators
• Be sure the site is clean, dry, not subject to flooding, and provided with adequate drainage in the event of heavy
rains.
• Be sure the location permits noise and vibration to be effectively isolated.
• Verify that the site provides easy access to the generator set for maintenance, repair, and firefighting purposes.
• Keep a minimum of five (5) feet of clearance around each side of the generator set to facilitate service or mainte-
nance.
• Be sure the location permits engine exhaust gases to be safely evacuated from inhabited or occupied areas.
Consider the direction of prevailing winds to prevent exhaust gases from being carried back to the engine area or
to the fresh air intake vents of nearby buildings.
• The site must allow for the provision of an adequate fuel supply.
• Be sure the location permits sufficient air flow for cooling and ventilation. Consider the proximity of any walls,
fences, or other noise abatement or security barriers. Do NOT face the radiator discharge end of the enclosure
into the prevailing wind.
• Consider cold weather kit options and accessories for the generator in cold weather locations.
• Verify that the unit is securely fastened to the mounting pad to prevent movement caused by vibration.
• Verify that all electrical connections have flexible sections to isolate vibration.
• Verify that the fuel pressure and pipe is sized correctly and that it has the appropriate flex hose.
NOTE: Failure to comply with the location guidelines can result in damage to the generator or surrounding area and
may cause the warranty to be suspended or voided. Extra repair labor or equipment may not be covered under the
warranty if service access is difficult or restricted.
2.6.2— Weather Considerations
Consider local weather conditions during installation. There are various accessories available to ensure fast, reliable
starting and operation regardless of local climatic conditions. Optional cold weather kits make starting of the engine
more dependable and reliable.
2.7 — Accessories
The following product accessories are available. Contact a Dealer for additional information.
1. Scheduled Maintenance Kit
2. Cold Weather Kit
3. Extreme Cold Weather Kit
4. Mobile Link
5. Mobile Link Harness Adapter Kit*
6. Wireless Local Monitor
7. Wireless Local Monitor Harness Adapter Kit*
8. Smart Management Module
9. Emergency Stop Switch
10. Base Plug Kit
11. Touch-Up Paint Kit
*Required for liquid-cooled applications