Installation Checklists
46 Installation Guidelines for Spark-Ignited Stationary Emergency Generators
Does the concrete pad extend beyond the frame rails at least six (6) inches (15.24 cm) on all sides?
Is the concrete pad flat and level to within 1/2 inch?
Are plugs installed in the tie-down holes of the frame rail?
If installed on a roof or combustible floor, is the generator seated on a layer of sheet metal and non-combustible
insulation? Do the sheet metal and insulation extend beyond the generator base at least six (6) inches (15.24 cm)
on all sides?
Is the base frame stub-up cover plate installed?
Do all fuel, coolant, exhaust, and electrical lines have flexible sections where they connect to the generator?
Is all piping properly supported and secured?
Do these parameters meet all applicable codes and local jurisdiction?
8.4 — Ventilation System Checklist
NOTE: See Chapter 4 for more information.
Is there sufficient air flow for cooling and ventilation?
Are all bushes, shrubs and other vegetation a minimum of 3 feet away?
Does the air inlet face the direction of prevailing winds?
Has system piping been properly sized? Have all gas loads been taken into consideration?
Has system been properly protected from freeze up and corrosion?
Have standby equipment heaters been specified?
Have system drain valves and air eliminators been installed?
Does the air outlet face noise sensitive areas without noise attenuating devices?
Does the installation appear to have the necessary accessories to enable fast, reliable starting and operation in
adverse weather conditions (such as engine block heaters, battery warmers, etc.)?
Do these parameters meet all applicable codes and local jurisdiction?
8.5 — Exhaust System Checklist
NOTE: See Chapter 5 for more information.
Are exhaust discharges directed away from combustible surfaces and inhabited areas?
Is exhaust piping kept clear of fuel supply, fuel lines, etc.?
Is off-engine exhaust piping covered with high temperature insulation blankets where necessary?
Do these parameters meet all applicable codes and local jurisdiction?