General Information
26 MGG100M Operating Manual 36833 C
Alarm and Warning Response Procedures
Acknowledging an alarm or warning silences the alarm horn and clears the record from the H-100 controller display.
Note: The manufacturer recommends notifying a GMPASD of any alarm/warning condition, so qualified service
personnel can examine the situation.
Shutdown alarms are cleared, as follows.
• Turn key switch to OFF
• Resolve conditions that caused the alarm
• On the H-100 control panel, acknowledge the alarm:
1. Go to the Alarms page.
2. Move the cursor to the ACK field.
3. Press ENTER.