Operation
36833 C MGG100M Operating Manual 29
Connecting Fuel Sources
After safely positioning the unit, connect the fuel sources.
Both fuel sources must be connected during unit installation on a work site. After installation and confirmation of
successful operation, both fuel sources should remain connected. Although the unit can operate with just one fuel
source connected, it is designed to switch fuels under certain circumstances; and if the unit attempts to switch fuels
without both sources connected, the unit may shut off, immediately stopping power to the output connections. See
Fuel System for more information.
Connect fuel sources as follows.
1. Select pipes appropriate for the required fuel flow rate.
See Pipe Diameter and Fuel Flow Rate.
2. Apply Gasolia® soft-set thread sealant with PTFE to threads of tapered ends of pipes.
Note: Do not apply sealant to flanged ends.
3. Connect pipes to fuel sources.
4. Connect pipes to fuel inlets on unit (see Figure 7).
5. Open valves at fuel sources.
6. Open valves on unit fuel inlet ports.
7. Verify the external fuel-filter drain ports (see Figure 7) are un-stopped and routed to suitable containers.