32 Owner’s Manual for Power Zone Pro Sync
Troubleshooting
CAN GOV1 MODULE ERROR SD Power Zone CAN bus Governor produced an
error. Can be numbered 1-4.
CAN AVR1 MODULE ERROR SD Power Zone CAN bus AVR produced an error.
Can be numbered 1-4.
CAN BAT1 MODULE ERROR AL Power Zone CAN bus Battery Charger produced
an error. Can be numbered 1-4.
CAN UNKNOWN MODULE ERROR SD An unknown Power Zone CAN bus module
produced an error
CAN GOV1 MODULE WARNING WN Power Zone CAN bus Governor produced a
warning. Can be numbered 1-4.
CAN AVR1 MODULE WARNING WN Power Zone CAN bus AVR produced a warning.
Can be numbered 1-4.
CAN BAT1 MODULE WARNING WN Power Zone CAN bus Battery Charger produced
a warning. Can be numbered 1-4.
CAN UNKNOWN MODULE WARNING WN An unknown Power Zone CAN bus module
produced a warning
CAN GOV1 ACK ERROR WN Power Zone CAN bus Governor acknowledged
an error. Can be numbered 1-4.
CAN AVR1 ACK ERROR WN Power Zone CAN bus AVR acknowledged an
error. Can be numbered 1-4.
CAN BAT1 ACK ERROR WN Power Zone CAN bus Battery Charger
acknowledged an error. Can be numbered 1-4.
CAN UNKNOWN ACK ERROR WN An unknown Power Zone CAN bus module
acknowledged an error
ETH BAD MAC WN Read invalid MAC address from internal
EEPROM
ETH BAD SWITCH WN Internal Ethernet Switch has failed
ETH OTHER ERROR WN An Ethernet error has occurred
LOST DISPLAY WN Power Zone Display has been lost or is
unresponsive
SPI2 ERROR WN Communication fault with NV memory
MCU CORE VERSION ERROR SD A/D Processor program missing
STACK OVERFLOW ERROR SD Microcontroller operating system stack overflow
detected
KEYSWITCH NOT SETUP SD See AI, AO, DI and DO XXX NOT SETUP
Alarms.
REMOTE START 1 NOT SETUP SD See AI, AO, DI and DO XXX NOT SETUP
Alarms.
MCB STATUS 1 NOT SETUP SD See AI, AO, DI and DO XXX NOT SETUP
Alarms.
Alarm Display Text Type Alarm Description