54 Owner’s Manual for Power Zone Pro Sync
Troubleshooting
INVALID DI
CONFIGURATION
FOR SHUTDOWN
BYPASS
Warning condition has occurred
as Activate Shutdown Bypass
digital input is not configured or
configured incorrectly.
When Shutdown bypass
has been enabled but
“Activate Shutdown Bypass
Digital input” has not been
configured as a Digital
input. An “Invalid DI
Configuration Shutdown
Bypass” Warning is set.
On the Digital Input
Configuration screen
configure the selected
input as “Activate
Shutdown Bypass” to
clear the warning. This
warning can also be
cleared by disabling the
Shutdown Bypass
setting on the Engine
Configuration screen.