Installation Manual for Generac PWRcell Battery 9
General Information
Battery Module Technical Data
Physical Characteristics DCB Battery EX Battery
Width 17.32 ± 0.08in (440 ± 2 mm)
Length 17.72 ± 0.08in (450 ± 2 mm)
Height 3.30 ± 0.08in (84 ± 2 mm) 3.46 ± 0.08in (88 ± 2 mm)
Weight 55.12 ± 0.1 lbs (25 ± 0.5 kg) 58.42 ± 0.1 lbs (26.5 ± 0.5 kg)
Electrical Characteristics DCB Battery EX Battery
Cell type LiNiMnCo
Usable Energy Capacity (Nominal) 3.0 kWh
Usable Battery Capacity (Nominal) 64.1 Ah 69.4 Ah
Nominal Voltage 46.8 VDC
43.2 / 44.4 VDC
1
Voltage Range 39 ~ 53.4VDC 33 ~ 50.4 VDC
DC Disconnect Fuse
Scalability (number of modules in series) 3 to 6
Shelf life or maximum self-discharge rate 6 months maximum storage time
BMS DCB Battery EX Battery
Monitoring parameters
System Voltage
System Current
Cell Voltage
Cell temperature
Communication RS-485
Operating Conditions DCB Battery EX Battery
Full Performance Temperature Range (Charging)
2
:
59 to 104°F (15 to 40°C)
Full Performance Temperature Range (Discharging)
2
:
32 to 104°F (0 to 40°C)
Maximum Operating Temperature Range (Charging)
2
:
41 to 122 °F (5 to 50°C)
Maximum Operating Temperature Range (Discharging)
2
:
14 to 122 °F (-10 to 50°C)
Storage Temperature -4 to 104°F (-20 to 40°C) -4 to 140°F (-20 to 60°C)
Altitude Max. 6,560 ft (2,000 m)
Cooling Strategy Natural Convection
Reliability & Certification DCB Battery EX Battery
Certificates
Cell: UL 1642
Battery Module: UL 1973
Transportation UN38.3
Ingress Rating IP20
Emissions FCC Part 15 Class B
Environmental
Battery Directive 2013 / 56 / EU
Reach
RoHS Directive 2011 / 65 / EU,
Rechargeable Battery Recycling
Act
1
Model G0080001 / Model G0080003 & G0080005.
2
See Figure 2-1 for a detailed battery deration curve by cell temperature.