Location and Compliance
16 Installation Manual for Generac PWRcell Battery
Do not install where leaves, snow, dirt, sand, or
other debris may block the air intake at the base of
the unit.
Do not install where grass, vines, ivy, landscape
plantings, or other vegetation may obscure access,
block vents, or intrude into the unit.
Do not install where excessive amounts of water
from roof runoff, landscape irrigation, water sprin-
klers, or sump pump discharge could contact the
enclosure.
Do not install where water levels may rise and con-
tact the unit.
Do not install within 36 in (91.44 cm) of any door or
window.
The installation site must meet the outdoor working
space requirements in NEC Article 110.26.
The PWRcell Battery is not intended for use in
mobile (RV) or portable applications.
Multiple battery units must be separated by mini-
mum 3 ft (91.44cm) between the units per NFPA
855.
See Table 3-1. Ensure minimum clearances are
met.
Operating Temperature Range and
Environmental Requirements
The PWRcell Battery can operate within the maximum
operating temperature range. For best performance,
install the PWRcell Battery in an environment where
ambient temperatures fall within the full performance
temperature range. The PWRcell Battery will limit or halt
charge / discharge power at extreme temperatures.
For hotter climates, install the battery out of direct sun-
light. Exposure to temperatures above the optimal tem-
perature range will impact battery performance.
For colder climates, install the battery in a conditioned
space. Exposure to temperatures below the optimal
ambient temperature range will impact battery perfor-
mance.
Compliance
Follow all instructions included in this manual and use
appropriate practices for all product wiring and installa-
tion.
NOTE: It is the responsibility of the installer to ensure
electrical worker safety, including conformance with lock-
out/tagout procedures for servicing PWRcell equipment.
(000190)
DANGER
Loss of life. Property damage. Installation must
always comply with applicable codes, standards, laws
and regulations. Failure to do so will result in death
or serious injury.
WARNING
Electrocution. Refer to local codes and standards for
safety equipment required when working with a live
electrical system. Failure to use required safety
equipment could result in death or serious injury.
(000257)
(000182a)
WARNING
Equipment damage. Only qualified service personnel may
install, operate, and maintain this equipment. Failure to
follow proper installation requirements could result in death,
serious injury, and equipment or property damage.

Table of Contents

Other manuals for Generac Power Systems PWRcell M3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems PWRcell M3 and is the answer not in the manual?

Generac Power Systems PWRcell M3 Specifications

General IconGeneral
BrandGenerac Power Systems
ModelPWRcell M3
CategoryCamera Accessories
LanguageEnglish

Related product manuals