Section 7: Touchscreen Display Operation and SettingsPage 24
7.3 CIRCUIT SETTINGS
Tapping the screen on the displayed information of the DHW
or a heating circuit you are viewing (if more than 1 heat circuit
installed) will open the circuit settings panel. This will display
various options that can be edited. Refer to Figure 7-4.
20,5°C
C
DHW temperature
°
53
53
55.0°COn
Figure 7-4: Circuit settings access on touch-screen
7.3.1.1 HEAT CIRCUIT SETTINGS
Entering Heat circuit settings will display options the used can edit
for the heating circuit. Refer to Figure 7-5.
Preset day temperature
Heating zone 1
+
-
°
.5
C
21
Figure 7-5: Heating circuit settings example
Figure 7-3: Thermostatically uncontrolled circuit display
! NOTE !
The circuit is not controlled by a thermostat if a heat
emitter icon is displayed on the circuit temperature display
screen.
20,5°C
First Floor
A
Auto
40°C
7.2 SMART CONTROLLER OPERATION
7.2.1 MAIN HEAT SOURCE
The Grant Aerona Smart controller manages the operation of the
heat pump by activating or deactivating it according to demand for
DHW or the space heating circuits.
7.2.2 HEAT CIRCUITS
The Grant Aerona Smart controller can manage the operation of
one non-adjustable and up to two adjustable heat circuits. Water
temperature in circuits can set as a xed ow temperature or
by weather, i.e., water temperature in the circuit is calculated in
accordance with a temperature from the external temperature
sensor. Despite varying outdoor temperature, a room temperature
in heated rooms is kept on a set level.
• Dependent circuits – A thermostat assigned for many circuits.
For example, temperature readings on a installed panel aect
operation of both radiator and underoor circuits. Commonly
one Thermostat in a central location.
• Independent circuit – Connecting thermostats to measure
room temperature independently and aecting assigned
circuits. It is the way to obtain independency of the circuits,
e.g., in case when one part of the building is used for the
whole year and the second part is used periodically, e.g., for
rent.
If multiple circuits are being controlled you can navigate between
them with a swipe of the screen either to the left or the right.
7.2.3 DOMESTIC HOT WATER
The Smart Controller manages the operation of the Heat Pump
and heating of a DHW cylinder up to a user set temperature. DHW
operation can be programmed in time intervals with a minimum
operation for disinfection mandatory. While the Smart Controller
can also control a DHW secondary circulating pump, their use is
not recommended to minimise wasted energy and running costs.
! NOTE !
The change of the colour under the current value of the
temperature of the circulation and DHW cylinder indicates
whether the temperature is below (blue), above (red) or the
same (green) as the target temperature. Grey indicates the
DHW function is O.
20,5°C
C
DHW temperature
°
53
53°C
,6
Figure 7-2: DHW temperature display example