Section 1: Introduction Page 5
2.1 WIRING CENTRE
Table 2-1: Technical Data
Grant Aerona Smart Controller - Wiring Centre
Power supply 230V AC, 50Hz
Controller current consumption 0.4 A
3
Maximum rate current 6 (6) A
Protection class IP 20
4
Ambient Temperature 0 to 50
o
C
Storage temperature 0 to 65
o
C
Relative humidity 5 to 85% without water vapour condensation
Outdoor Weather Sensor working range -40 to 110
o
C
Measurement accuracy: Water & Outdoor Weather Sensors ±2
o
C
Wiring centre dimensions 234mm x 225mm x 64mm
Standards EN 60730-2-9. EN 60730-1
Software class A, according to EN 60730-1
Protection class IP 20
Installation method Wall mounted
3
Current consumed only by the controller. Overall current consumption depends on number of devices
4
After installing all cable clamps.
2 Technical Data
234 mm
225 mm
I
0
64 mm
225 mm
Figure 2-1: Wiring centre dimensions