Section 8: Service Settings - InstallerPage 32
Parameter Description
Circuit 1 This menu contains parameters related to operating the non-adjustable circuit. The non-adjustable circuit 1 preset temperature
will be automatically increased in order to guarantee heat for adjustable circuits 2 and 3.
• Circuit support - turn on or o circuit support.
• Circuit name - name of the circuit set by user.
• Circuit type - This menu contains parameters related to selecting the type of a non-adjustable circuit.
- Radiators
- Fan-coil
• Regulation Method
- Fixed - constant set temperature of water in the non-adjustable circuit is maintained.
- Weather - Water temperature is related to Outdoor weather sensor. Outdoor weather sensor required
• Work Mode
- OFF
- Day – setting higher target circuit temperature.
- Night – setting lower target circuit temperature.
- Schedule – Day or Night mode is set depending on the time schedule.
• Heating circuit - switching the Heating Circuit On/O.
• Fixed preset water temperature - Heat pump stops when xed preset water temperature is reached.
• Decreasing xed water temperature - If Regulation method is xed value of temperature decrease for night mode.
• Heating Curve - View and adjust the heating curve for the circuit if the circuit is weather compensated
• Decrease water temperature - Flow temperature drop when in night mode if the circuit is weather compensated.
• Thermostat - Thermostat in control of circuit. Assignable options: None, Room panel, Wireless thermostat, Wired
thermostat.
• Room temperature correction – with thermostat support enabled automatic correction of room temperature is carried out
in accordance with the following formula:
- Target temperature with correction = Target temperature of the circuit + (Target temperature of the thermostat
assigned to the circuit minus Current temperature of the thermostat assigned to the circuit) x Room temperature
correction.
- By default, the Room temperature correction value is 4.0, and the value range is 0 - 10. It is necessary to nd
appropriate value of the Room temperature correction. The higher the coecient, the greater the correction of
target circuit temperature. If the setting is “0”, the target circuit temperature is not corrected. Note: setting a value of
the room temperature coecient too high may cause cyclical uctuations of the room temperature.
• Thermostat Pump Blockade - Parameters for the circuit pump being disabled when a room thermostat is active for the
circuit. Refer to Section 7.8.
- OFF - When the target air temperature is met or exceeded, the circuit pump is not disabled.
- ON - When the target air temperature is met or exceeded, the circuit pump is disabled.
Circuit 2 & 3 Circuit 2 & 3 contain similar functions to Circuit 1 and are dynamic based on the congured system. Below are additional
options for Circuit 2 and 3.
• Circuit type - This menu contains parameters related to selecting the type of a adjustable circuit.
- Radiators
- Fan-coil
- Underoor heating
• Pump only - Enables or disables the mixing function on the circuit.
- No – The circuit is mixer controlled. (Options for Mixer setup will be available in the Circuit menu)
- Yes – The circuit is not mixer controlled. (Circuit stop from preset temp will become active).
• Circuit stop from preset temp - Parameters for a circuit pump being disabled based on water temperature values.
- No – When the target water temperature value is exceeded, the circuit pump/valve is not disabled.
- Yes – when the target water temperature value is exceeded, the circuit pump/valve is disabled.
• Minimum temperature - Minimum target water temperature in the adjustable circuit.
• Maximum temperature - Maximum target water temperature in the adjustable circuit. If the Maximum temperature is
greater than 60°C, the controller will take 60°C as a maximum value.
• Valve opening time - The time between fully open and closed on installed mixing valve.
• Mixer deadband zone - Temperature insensitivity of mixer adjustment.
• Proportional Range - Mixer actuator proportional movement.
• Integration time constant - Time for actuator reaction for temperature deviation.
Heaters This menu contains parameters related to the operation of the DHW heater and buer heater support.
• Buer heater - enabling or disabling the buer heater support.
• Buer heater (delay) - delay time for switching on the buer heater after a heat pump demand.
• DHW heater - enabling or disabling the DHW heater support. Output to Smart Immersion Relay. Refer to
• DHW heater (delay) - delay time for DHW heater ON from DHW demand start.
The options below apply to both buer and/or DHW heater support when congured.
• Outside temp to activate the heater - external temperature value beyond which the DHW heater will be activated.
• Outside temp force the heater - external temperature value at which the heater support will be permanently switched on
during heat pump operation.
Flow meter This menu contains parameters related to the operation of the ow meter operation and the detection of no ow. Refer to
Appendix E.
• Flow meter - Flow detection is performed by selected option. (Default/Pulse)
• Default ow meter - default ow in the circuit, when exceeded, a no-ow alarm will be reported.
• Specic Heat Capacity - Coecient of liquid used to transfer heat.
• Time detect - time after which the no-ow alarm will be reported.
• Time alarm erase - time after which the no-ow alarm will be reset. The controller will not report an alarm.
• No ow detection threshold - ow value below which the alarm “Flow error” will be reported.
• No ow detection hysteresis - if the actual ow rises above the value of No ow detection threshold plus No ow detection
hysteresis, the “Flow error” alarm will be turned o.
• Pulse rate - Flow sensor pulse rate to calculate ow.
• Pulse counting time - Flow sensor pulse count time duration.
• Too often alarm - too frequent no-ow alarm detection threshold. It allows to limit the frequent reporting of the no-ow
alarm.
Default Settings This menu saves and recalls stored defaults applied by the consumer.
• Restore default settings - Recall and apply saved default settings.
• Save current settings as default - Saves the current setup of the Grant Aerona Smart controller to memory.