EasyManuals Logo

Grant HPiD6 User Manual

Grant HPiD6
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
Section 6: ElectricalPage 24
Cable and circuit breakers should be to EN Standards.
NOTE
!
Table 6-5: Power supply cable and breaker capacity
Model
Power supply cable (mm²)
Breaker
capacity
Maximum Minimum
HPID6 2.5 1.5 16A Class C
HPID10 4.0 2.5 20A Class C
HPID16 6.0 4.0 32A Class C
In the case of long cable runs, selection of correct cable must
be done in accordance with BS 7671 (IET Wiring Regulations)
NOTE
!
Strip ends of connecting cables in accordance with Figure 6-6.
Crimp terminals with insulating sleeves can be used if required
as illustrated in the diagram below for connecting the wires to the
terminal block. Stranded conductors shall not be soldered.
• Use a circuit breaker with a 3 mm clearance of air gap between
the contacts.
• Be sure to FULLY insert the cable cores into the proper position
of the terminal block.
• Faulty wiring may cause not only abnormal operation but also
damage to PCB board.
• Fasten each terminal screw securely.
• To check the connections are secure, pull the cable slightly.
10 mm 30 mm
Terminal block
Crimp terminal
Stripped wire :10mm
Sleeve
Crimp terminal
Sleeve
PCB(Terminal)
Figure 6-6: Stripping the cables
It is important that the cable is stripped back 10mm.
If shorter, it is possible to clamp down onto the insulation.
If longer, a short circuit may occur.
!
CAUTION
Lockable
isolator
Consumer
unit
Figure 6-4: Heat pump, isolator and consumer unit

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grant HPiD6 and is the answer not in the manual?

Grant HPiD6 Specifications

General IconGeneral
BrandGrant
ModelHPiD6
CategoryHeat Pump
LanguageEnglish

Related product manuals