9
Rest room 80~100
Lounge (no
smoking area)
160~250
Bank
Business hall 120~160
Lounge for
judges, coaches
and athletes
100~140
Office 70~120
Office
building
Deluxe office 120~160
Machine
room
120~160
Average office
90~120
Exhibition hall 150~200 Machine room 100~140
Auditorium 160~240
Meeting room
150~200
Multi-functional room 180~250
Reception room
(smoking area)
180~260
Library
Reading
room
100~160 Hall and rest room 70~110
Service
section
90~110
Office building
95~115
Stack room 70~90
Super high-rise building
105~145
Special
collection
room
100~150
Residen-
tial
building
Multi-storey
building
88~150
Restau-
rant
Hall 200~280
High-rise
80~120
Individual
dining room
180~250 Villa 150~220
Supermar-
ket
Service Hall 160~220
Meet and fish
area
90~160
Note: it is cited from Practical Heating and Air Conditioning Design Manual
Table 3.6.2 Cooling and Heating Load per Unit of Air Conditioning Area
Construction type
Heating and Cooling Load
(W/m
2
)
Loading Conditions
Total
cool-
ing
ca-
pacity
Fres-
h air
Total
heat-
ing
ca-
pacity
Fresh
air
Light-
ing
(W/
m
2
)
Den-
sity
(p/
m
2
)
Fresh
air
(m
3
/
h)
Exfil-
tration
(h-
1)
Bank Business Hall 242 72 220 90 50 0.3 6 1.5
A Series Modular-type Air-cooled (Heat Pump) Chiller