3.6.1.6 A case for Selection
Background: there is an office building covering 12,000 totally with 10,500 to be air
conditioned, among which the big meeting rooms take up 500, the small meeting rooms take
up 1,500 and office rooms take up 8,500, and fresh air is required.
(1)Calculate the cooling load
1) By the estimated cooling load:
Big meeting rooms: 500×180W/㎡)=90000W=90kW
Small meeting rooms: 150×240W/㎡)=360000W=360kW
Offices: 8600×150W/㎡)=1290000W1290kW
Total: 90kW360kW1290kW=1740kW
2) By the building area:
12000×98W1176kW
3) According to the calculation results of 1) and 2), cooling load 1740kW is selected.
(2)Calculate the heating load
By the estimated heating load:
12000×70=840000W=840kW
(3)Select the desired model and quantity
Look up the GREE Technical Guide Manual and it is concluded that 29 SQWRF60VM/
NaA-M meet the design requirement (cooling load: 1740kW,, heating load: 1885kW).
A Series Modular-type Air-cooled (Heat Pump) Chiller