GREE GMV5 INDOOR UNIT SERVICE MANUAL
182
4.14 Concealed Floor Standing Type
Note:
The following steps are specific for GMV-ND56ZA/A-T units. For other units, the assembly and
disassembly procedure is similar except the specifications of centrifugal fans and motors.
Motor and fan
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
1. Remove the line
connecting to the motor.
●Use a screwdriver to unscrew the
electric box cover.
●Remove from the master board
the line connecting to the motor
and remove the tie.
2. Remove the filter.
●Remove the filter from the air
return frame.
3. Remove the air return
cover plate.
●Use a screwdriver to unscrew the
air return cover plate.
4. Remove the bottom cover
plate.
●Use a screwdriver to unscrew the
air return cover plate.
5. Remove the rear volute
casing.
●Loosen the fasteners that
connect the rear volute casing with
the front volute casing and remove
the rear volute casing.