GREE GMV5 INDOOR UNIT SERVICE MANUAL
26
3.12 Console Type Indoor Unit
Model
GMV-ND22C/A-
T
GMV-ND28C/A-
T
GMV-ND36C/A-
T
GMV-ND45C/A-
T
GMV-ND50C/A-
T
Horse Power
HP
1
1
1.5
2
2
Cooling capacity
kW
2.2
2.8
3.6
4.5
5.0
Heating capacity
kW
2.5
3.2
4.0
5.0
5.5
Air volume
m
3
/h
450
500
600
630
650
Cooling power input
W
15
15
20
40
40
Cooling current input
A
0.17
0.17
0.25
0.25
0.4
Heating power input
W
15
15
20
40
40
Heating current input
A
0.17
0.17
0.25
0.25
0.4
*Minimum line current
A
0.16
0.16
0.16
0.16
0.16
*Maximum fuse current
A
6
6
6
6
6
Sound pressure level
dB(A)
36
38
40
43
46
Power supply
220-240V 1 phase ~50Hz/208-230V 1 phase ~60Hz
Piping
interface
Liquid pipe
mm
6.35
6.35
6.35
6.35
6.35
Gas pipe
mm
9.52
9.52
12.7
12.7
12.7
Drain pipe
External diameter
× thickness
mm
Φ17.2×1.0
Φ17.2×1.0
Φ17.2×1.0
Φ17.2×1.0
Φ17.2×1.0
Dimensions
W×H
mm
700×215×600
700×215×600
700×215×600
700×215×600
700×215×600
Net weight
kg
16
16
16
16
16
Notes:
Rated Cooling capacity test conditions: indoor 27°C DB/19°C WB, outdoor 35°C DB; connection
pipe length: 5 m, without height drop between units
Rated heating capacity test conditions: indoor 20°C DB, outdoor 7°C DB/6 °C WB; connection
pipe length: 5 m, without height drop between units
Floor type