GREE GMV5 INDOOR UNIT SERVICE MANUAL
76
to enter the wired controller engineering parameter setting interface. The temperature area
displays P00.
(2) Select a parameter code by pressing or . Press the MODE button to switch to
parameter value settings. The parameter value blinks. Adjust the parameter value by pressing
or and then press the SWING button to complete settings.
(3) Press the SWING button to return to the upper-level menu till quitting parameter settings.
For the engineering parameter setting list of the XK49 wired controller, refer to the engineering setting
query list in
XK46 engineering parameter settings
.
Note:
In parameter settings, the function of SWING on the XK49 wired controller is equivalent to the
function of ENTER/CANCEL on the XK46 wired controller.
5.3 Engineering Application Functions Operated through the
XK79 Wired Controller
5.3.1 Master IDU Settings
The master IDU can be set through the wired controller or remote controller. The methods for setting
the master IDU through the wired controller are as follows:
Method 1:
Step 1: Set an IDU to power-off status.
Step 2: Press and hold the MODE button on the wired controller for more than five seconds.
Step 3: Check whether the setting is successful. If it is, MASTER on the wired controller will be on.
Otherwise, repeat steps 1 and 2.