GREE GMV5 INDOOR UNIT SERVICE MANUAL
12
Model
GMV-ND100L/A-T
GMV-ND140L/A-T
Liquid
mm
Φ9.52
Φ9.52
Connection Method
Bell mouth connection
Bell mouth connection
Net weight
kg
54
57
Note:
Units conform to design standard: ISO 15042-2011.
Specifications may be changed due to product improvement. Please refer to nameplates of the
units.
Noise data are collected from a semi-anechoic room. Decibels may be slightly higher in actual
operation due to environmental change.
Above parameters are tested under the condition: high fan speed.
Cooling: Indoor air temperature 27°C DB/19°C WB.
Heating: Indoor air temperature 20°C DB/15°C WB.
3.2 High Static Pressure Duct Type
Model
GMV-
ND56PHS/A-
T
GMV-
ND63PHS/A-
T
GMV-
ND71PHS/A-
T
GMV-ND80
PHS/A-T
GMV-ND90
PHS/A-T
GMV-
ND100PHS/A-T
Horse Power
HP
2
3
3
3
4
4
Cooling capacity
kW
5.6
6.3
7.1
8.0
9.0
10.0
Heating capacity
kW
6.3
7.1
8.0
9.0
10.0
11.2
Air volume
m
3
/h
1000
1000
1100
1100
1700
1700
Static pressure (Pa)
Standard
70
70
70
70
70
70
Optional
0~100
0~100
0~100
0~100
0~100
0~100
Cooling power input
W
120
120
130
130
200
200
Cooling current input
A
0.6
0.6
0.6
0.6
1.0
1.0
Heating power input
W
120
120
130
130
200
200
Heating current input
A
0.6
0.6
0.6
0.6
1.0
1.0
Minimum line current
A
0.75
0.75
0.75
0.75
1.25
1.25
Maximum fuse
current
A
6
6
6
6
6
6
Sound pressure level
dB(A)
44
44
45
45
46
46
Power supply
220-240V 1 phase ~50Hz/208-230V 1 phase ~60Hz
Connection
pipe
Liquid
pipe
mm
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Φ9.52
Gas pipe
mm
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Φ15.9
Φ15.9