No AC Connection No Utility
Please confirm grid is lost or not.
Check the grid connection is good or not.
Check the switches on the cable are on or not.
Output High DCI
Output DC current too high.
Please refer to the local grid
standard for disconnection time
when the output DC current is
too high.
Restart inverter.
Please contact Growatt service center if restart can’t
solve the problem.
Bat Voltage High Battery Voltage higher than 60V
Check the voltage of battery is in the range of
specification or not.
Check the battery connection is right or not
If battery is really higher than 60V. Please disconnect
the connection of battery and check inverter.
Bat Voltage Low Battery Voltage Lower than 42 V
Check the real voltage of battery.
Check the wire of battery and inverter is good or
not.
BMS Warning:XXX BMS report warning
Check the warning information from lithium battery
user manual.
Please contact Growatt service center if restart can’t
solve the problem.
BMS error:XXX BMS report error
Check the warning information from lithium battery
user manual.
Please contact Growatt service center if restart can’t
solve the problem.
EPS Volt Low EPS output voltage low
Check the load of EPS. If overload occurred, reduce
load.
Restart inverter again.
Error Message
Error Message Description Suggestion
Error 411 Internal communication failed
Restart inverter.
Please contact Growatt service center if restart can’t
solve the problem.
Error 417 Sample fault
Restart inverter
Please contact Growatt service center if restart can’t
solve the problem
Error 418
DSP and COM firmware version
unmatch, system fault.
Read DSP and COM firmware version from LCD or
shinebus.
Check if the firmware is correct.
Error 303
Inverter L N reversed or ground
failed
Check the L line and N line is reversed or not.
Check the PE s connected well or not.

Other manuals for Growatt SPH4000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Growatt SPH4000 and is the answer not in the manual?

Growatt SPH4000 Specifications

General IconGeneral
ModelSPH4000
CategoryInverter
Rated Power4000 W
Max. DC Voltage550 V
MPPT Voltage Range120 V - 500 V
Number of MPPTs2
AC Output Voltage230 V
Frequency50/60Hz
Efficiency97.5%
Start Voltage150 V
Nominal DC Voltage360V
Max. Input Current per MPPT11 A
AC Nominal Power4000 W
Max. AC Apparent Power4000 VA
AC Voltage Range180 V - 280 V
Power Factor0.8 leading to 0.8 lagging
THDi<3%
AC Connection TypeSingle phase
Max. Charge/Discharge Power4000 W
Nominal Battery Voltage48 V
Communication with BMSCAN/RS485
Operating Temperature Range-25°C to +60°C
Protection DegreeIP65
TopologyTransformerless
Weight25 kg
Max. PV Input Voltage550 V
Cooling MethodNatural Convection