5.Installation
5.1 Basic Installation Requirements
A. Ensure that the installation surface is solid enough to bear the weight of the WIT Inverter.
(Refer to Table 3.2 for the weight of the WIT Inverter)
B. Ensure that the installation position is suitable for the dimensions of the WIT Inverter.
C. Do not install the WIT Inverter in areas with flammable or thermolabile materials.
D. The WIT Inverter is protected to IP66 and can be installed indoors or outdoors.
E. Do not expose the WIT Inverter to direct sunlight. Otherwise, excessive temperature may
lead to power reduction.
F. Keep the humidity at 0% to 95% RH.
G. Keep the ambient temperature at -30℃ to 60℃.
H. The WIT inverter can only be vertically mounted on a flat ground or a vertical wall. Please
refer to the following figures:
Fig 5.1
I. Reserve enough clearance around the WIT Inverter to ensure sufficient space for heat
dissipation and operation. Ensure that there are no objects within 1 m of the left, right and top
of the WIT Inverter; In ground-mounted installation, keep the back of the chassis at least 0.1
m away from the wall surface to ensure the performance of the WIT Inverter.
Fig 5.2
J. Keep the WIT Inverter away from strong interference sources.
K. Ensure that the WIT Inverter is not accessible to children.