2. Disconnect the DC switches on the WIT inverter, the AC breaker and the DC switch on the
battery;
3. Take out the battery terminals from the accessory kit delivered with the package. See Packing
List in Section 4;
4. Open the cover plate on the right side of the inverter, the position of which is shown in Fig 6.1.
Procedure for connecting the main battery power:
1. Connect the ground cable to the battery power ground bar, as shown in Fig 6.6;
2. Strip 18-20 mm of the insulation layer of the DC cables;
3. Crimp the battery cables and the battery terminals using crimping pliers, and then tighten the
insulation sleeve;
4. Connect the battery cables to the battery terminals on the inverter, as shown in Fig 6.6;
5. After connecting the main battery power cables, bind power cables at the reserved position, as
shown in Fig 6.6.
Fig 6.6 Position of the battery terminals
NOTE:
1. Connect the ground cable before connecting the battery cable; the ground point is shown in Fig 6.6.
2. Bind the battery power cables at the designated place after connecting them to the WIT Inverter
3. Lock the right cover plate after connecting the cables.
6.4.2 Connecting the Battery BMS-AC Terminal
NOTE: Perform operations according to on-site requirements.
Procedure for connecting the battery BMS-AC terminal:
1. Open the cover plate on the right side of the inverter, the position of which is shown in Fig 6.6;
2. Find the corresponding terminals from the accessory kit. Refer to Table 6.3 to connect the
terminals;
3.Remove the dustproof cover from the BMS-AC terminal, insert the terminals that have been
crimped with cables to the BMS-AC terminal, and tighten them.