EasyManua.ls Logo

Growatt WIT 50-100K-US - Monitoring Device Terminal

Growatt WIT 50-100K-US
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
6.5.4 Monitoring Device Terminal
The WIT 50-100K-US Storage/Hybrid inverters support remote monitoring when working with
the optional WiFi&LAN datalogger or the WiFi&4G datalogger. If the WiFi&LAN datalogger is
used, you need to connect a WiFi antenna and a network cable. If the WiFi&4G datalogger is used,
you need to connect a WiFi antenna and a 4G antenna. The installation steps are as follows:
For the WiFi & LAN datalogger:
1. Remove the waterproof cover from the ANT1 port, then plug the WiFi antenna into the jack and
screw tight. Please ensure that the antenna is correctly and securely connected.
2. Remove the waterproof cover of the LAN port and plug the network cable into the jack.
For the WiFi&4G datalogger:
1. Remove the waterproof cover from the ANT1 port then plug the WiFi antenna into the jack and
screw tight.
2. Remove the waterproof cover from the ANT2 port and plug the 4G antenna into the jack. Note:
1. Please ensure that the WiFi antenna, the 4G antenna and the network cable are connected to the
correct port and securely in place. Otherwise, the monitoring function might fail.
2. If the monitoring device is removed, please reinstall the waterproof cover to avoid water
penetration.
Fig 6.14 Connecting the monitoring device
6.5.5 DRMS Port
The WIT 50-100K-US Inverters have a DRMS port. Users can choose to connect this terminal if
required by local regulations. The connection procedure is as follows:
Connect the communication cable to the port as required. The DRMS port is a standard RJ45
terminal block, so you can follow the Ethernet cable connection method.
2. Remove the dustproof cover from the DRMS port and check whether there is a waterproof
silica gel pad. Insert the cable and tighten the rubber ring to prevent loose connection.