11. Decommissioning the WIT Inverter
Handle the WIT Inverter that will not be operated in the future properly.
1> Disconnect the external AC circuit breaker and prevent accidental reconnection due to
improper operation.
2> Set the DC switches to the OFF position.
3> Disconnect the upstream battery circuit breaker.
4> Wait at least 5 minutes before performing operations on it.
5> Disconnect the AC output power cables.
6> Disconnect the DC input power cables.
7> Remove the inverter from the bracket.
8> Dispose of the inverter according to local disposal rules.