3. After the cable connection, reinstall the dustproof cover. The position of the DRMS port is
shown in Fig 6.15 below.
Fig 6.15 DRMS port
Table 6.9 Demand Response Modes (DRMs)
Socket asserted by
shorting pins
Operate the disconnection device
Do not consume at more than 50% of rated power
Do not consume at more than 75% of rated power AND Source reactive
power if capable
Increase power consumption (subject to constraints from other active DRMs)
Do not generate at more than 50% of rated power
Do not generate at more than 75% of rated power AND Sink reactive power
if capable
Increase power generation (subject to constraints from other active DRMs)
6.5.6 Rapid Shutdown Device (RSD)
The Rapid Shutdown Device (RSD) is used to shut down the WIT 50-100K-US system and stop
the PV side from supplying power to the inverter. The RSD is a normally closed (NC) contact.
Once the RSD button is pushed, the inverter will be disconnected from the PV side and shut down.