Fig 6.15 Rapid shutdown device (RSD)
Installation:
1. Unscrew the four plastic screws assembled on the RSD in the accessory kit using a cross-head
screwdriver.
2. Drill four holes in the wall using an electrical drill with an M6 drill bit.
3. Insert the four green plastic pipes into the holes.
4. Align the RSD with the hole positions and screw the 4 self-tapping screws into the pipes
Fig 6.15 Installing the RSD
Connect the cables (18-22 AWG) crimped with the pipe-shaped terminal to Pin 12 and Pin 13 of
COM1 port as the figure below shows. Open the cover of the RSD, route the other end of the
cables through the hole on the RSD and connect them to the RSD contact. Reinstall the cover and
secure it with screws.
NOTE:
1. Before powering on the WIT, please pull the button up to ensure that the RSD is at the NC
contact.
2. It’s recommended that the RSD be installed in a convenient place for the ease of operation.