EasyManua.ls Logo

Growatt WIT 50-100K-US - Parallel Communication Connection

Growatt WIT 50-100K-US
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
Fig 6.11 COM1 communication connection
3. The external communication terminals of the WIT 50-100K-US Inverters are described in Table
6.5. Short Pin 5 and pin 10 when the host computer is used.
Table 6.5 External communication terminal description
Definition of battery communication terminal
Number
Definition of signal
Note
1
PCS_RS485A_4
RS485_4
2
PCS_RS485B_4
3
RS485A1
RS485 terminal for external communication
4
RS485B1
5
Res_RS4851A
RS485 matching resistor
6
RS485A2
RS485 input port for the meter
7
RS485B2
8
RS485A2
RS485 output port for the meter
9
RS485B2
10
Res_RS4851B
RS485 matching resistor
11
PE
Grounding
12
REPO1
The WIT Inverter shutdown input dry contact
signal
13
REPO2
14
DO1
Generator start-up output dry contact signal
15
DO2
16
PE
Grounding
6.5.3 Parallel Communication Connection
The parallel signal terminal (COM2) of WIT 50-100K-US Inverters uses a 30-pin terminal. The
matching terminal is in the accessary kit. The connection steps are as follows:

Table of Contents

Related product manuals