EasyManua.ls Logo

Grundfos MAGNA3 Series - 5.4 Connection Diagram

Grundfos MAGNA3 Series
153 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13
English (US)
5.4 Connection diagram
Fig. 14 Example of typical connection, 1 x 230 V ± 10 %, 50/60 Hz
5.4.1 Connection to external controllers
Fig. 15 Example of connections in the control box
Concerning demands on signal wires and signal transmitters, see
section 19. Technical data.
Use screened cables for external on/off switch, digital input,
sensor and setpoint signals.
TM03 2397 0312
External switch
Fuse
(min. 10 A, time lag)
GFCI
Note
Note
All cables used must be connected in accordance with local regulations.
TM05 2673 3812
NC NO C NC NO C
NL
S/S
M
I
M
A
signal
sensor
Vcc
24V
IN
Mains
connection
Alarm
Operation
Start/
stop
On/off timer
Analog input
Warning
Wires connected to supply terminals, outputs
NC, NO, C and start/stop input must be separated
from each other and from the supply by
reinforced insulation.
Note
Note
All cables used must be heat-resistant up to
+185 °F (+85 °C).

Table of Contents

Other manuals for Grundfos MAGNA3 Series

Related product manuals