Guardian 5240 - No Retransfer to Utility Power; Problem 7 - Blown F1 or F2 Fuse; Starts When Loss of Utility Occurs, Generator Shuts down When Utility Returns but There Is no Retransfer to Utility Power

Guardian 5240
151 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
“V-TYPE” PREPACKAGED
TRANSFER SWITCHES
SECTION 3.3
TROUBLESHOOTING FLOW CHARTS
PART 3
Page 65
TEST 29 - CHECK
VOLTAGE ATUTILITY
CLOSING COIL C1 AND
LIMIT SWITCH XA1
TEST 24 - CHECK
MANUAL TRANSFER
SWITCH OPERATION
TEST 26 - CHECK
#23 AND #194
WIRING
CONNECTIONS
TEST 23 - TEST
TRANSFER
RELAY
TEST 32 -
CONTINUITY TEST
OF WIRING (C1)
TEST 31 -
TEST LIMIT
SWITCH XA1
GOOD
GOOD
GOOD
GOOD
BAD
BAD
BAD
C1 COIL VOLTAGE
GOOD BUT NO
TRANSFER
C1 COIL VOLTAGE
BAD / LIMIT
SWITCH XA1
VOLTAGE BAD
REPAIR OR
REPLACE
REPLACE
REPLACE
LIMIT
SWITCH
REPLACE
UTILITY
COIL C1
REPAIR
WIRE #A
Problem 6 - In Automatic Mode, Generator Starts When Loss of Utility Occurs, Generator Shuts
Down When Utility Returns But There Is No Retransfer To Utility Power
C1 COIL VOLTAGE
BAD / LIMIT
SWITCH XA1
VOLTAGE GOOD
TEST 30 - CHECK
FUSE F1 & F2
TEST 34 - CHECK
N1 & N2 WIRING
TEST 35 - CHECK
TRANSFORMER TX
GOOD
GOOD GOOD
BAD
BAD
BAD
REPAIR OR REPLACE
REPLACE
FINISH
FINISH
Problem 7 - Blown F1 or F2 Fuse