66
PME-MP60/MP07
A0616-13.4 enHBM
7.8 Examples
Example 1:
Reading the net measured value as a floating value using SDO transfer from
the amplifier with Module address 3.
Protocol at the amplifier:
Identifier
1st
byte
2nd byte
3rd byte
4th byte
5th byte
6th
byte
7th
byte
8th
byte
0603
40
01
30
01
X
X
X
X
CAN
identifier
Read
Index low
byte
Index
high byte
Subindex
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
don’t care
Response from amplifier:
Identifier
1st byte
2nd byte
3rd byte
4th byte
5th byte
6th
byte
7th
byte
8th
byte
0583
43
01
30
01
m0
m1
m2
m3
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
CAN
identifier
Read
Acknowl
edgeme
nt
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁÁ
Index low
byte
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁ
Index
high byte
Subinde
x
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Low byte High
byte
Measured value as floating
Example 2:
Setting the filter frequency to 200 Hz.
Protocol at the amplifier:
Identifier
1st byte
2nd byte
3rd byte
4th
byte
5th byte
6th
byte
7th
byte
8th
byte
0603
2B
90
21
01
BB
03
X
X
CAN
identifier
Write
2byte
Index
low byte
Index
high byte
Subin
dex
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
Low byte High byte
958 = (3BF Hex)
don’t care
Response from amplifier:
Identifier
1st byte
2nd byte
3rd byte
4th byte
5th byte
6th
byte
7th
byte
8th
byte
0583
60
90
21
01
X
X
X
X
CAN
identifier
Write
Acknowle
dgement
Index low
byte
Index
high byte
Subindex
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁ
don’t care