5 Inputs HIMatrix
Page 30 of 72 HI 800 023 E Rev. 1.01
F35 controller
Range of values in the application
Input
channels
Meas-
urement
procedure
Current, volt-
age
FS1000
1)
FS2000
1)
Safety-related
accuracy
8 Unipolar 0...+10 V 0...1000 0...2000 2 %
8 Unipolar 0...20 mA
0...500
2)
0...1000
3)
0...1000
2)
0...2000
3)
2 %
1)
can be configured by selecting the type in the PADT
2)
with external 250 Ω shunt adapter, part number: 98 2220059
3)
with external 500 Ω shunt adapter, part number.: 98 2220067
Table 16: Analog Inputs of the F35 Controller
F3 AIO 8/4 01 remote I/O
Input
channels
Meas-
urement
procedure
Current, volt-
age
Range of values in the application
Safety-related
accuracy
8 Unipolar 0...+10 V 0...2000 2 %
8 Unipolar 0...20 mA
0...1000
1)
0...2000
2)
2 %
1)
with external 250 Ω shunt adapter, part number.: 98 2220059
2)
with external 500 Ω shunt adapter, part number.: 98 2220067
Table 17: Analog Inputs of the F3 AIO 8/4 01 Remote I/O
F60 controller
Range of values in the application
Input
channels
AI 8 01
Meas-
urement
procedure
Current, volt-
age
FS1000
1)
FS2000
1)
Safety-related
accuracy
8 Unipolar -10...+10 V -1000...1000 -2000...2000 1 %
8 Unipolar 0...20 mA 0...1000
3)
0...2000
3
1 %
8 Unipolar 0...20 mA 0...500
2)
0...1000
2)
4 %
4 bipolar -10...+10 V -1000...1000 -2000...2000 1 %
MI 24 01
24 Unipolar 0...20 mA 0...2000
4)
1 %
1)
can be configured by selecting the type in the PADT (F60)
2)
with 250 Ω external shunt, part number: 00 0710251
3)
with 500 Ω external shunt, part number: 00 0603501 (accuracy 0.05%, P 1 W)
4)
internal shunts
Table 18: Analog Inputs of the F60 Controller
The module AI 8 01 of the HIMatrix F60 can be configured in the user program for eight
unipolar or four bipolar functions. However, the mixing of functions on a module is not
permitted.
The analog inputs of the F35 controller, the F3 AIO 8/4 01 remote I/O and the AI 8 01
module operate with voltage measurement. With the analog inputs of the HIMatrix F35 and
F3 AIO 8/4 01, digital outputs of the own system (F35) or of other HIMatrix controllers can
be monitored to detect open-circuits. Further information is available in the manuals of the
corresponding HIMatrix controllers.
If an open-circuit occurs (the line is not monitored by the system), any input signals are
processed on the high-resistance inputs. The value resulting from this fluctuating input