7 Start-Up  System Manual Modular Systems 
Page 56 of 114  HI 800 191 E Rev. 2.02 
Setting for safe 
operation 
All the switches/parameters listed below OFF 
can be changed online using the PADT. 
These parameters may 
not be changed online 
  System ID 
  Autostart 
  Global Forcing 
Allowed 
  Global Force 
Timeout Reaction 
  Load Allowed 
  Reload Allowed 
  Start Allowed 
These parameters may 
be changed online if 
Reload Allowed is set 
to ON. 
  Watchdog Time (for 
the resource) 
  Safety Time 
  Target Cycle Time 
  Target Cycle Time 
Mode 
If Reload Allowed is set 
to OFF, they are not 
changeable online. 
Allow Online Settings can only be set to ON if 
the PES is stopped. 
If the processor module is connected to the 
supply voltage, the user program starts 
automatically 
The user program does not start automatically 
after connecting the supply voltage. 
A cold start or warm start permitted with the 
PADT in RUN or STOP 
Configuration download is allowed 
Configuration download is not allowed 
Only applicable with F*03 devices/modules! 
Configuration reload is allowed 
Configuration reload is not allowed. 
A running reload process is not aborted when 
switching to OFF 
Global forcing permitted for this resource 
Global forcing not permitted for this resource 
Global Force 
Timeout Reaction 
Specifies how the resource should behave when the global 
force timeout has expired: 
  Stop Forcing 
  Stop the Resource 
Minimum 
Configuration 
Version 
With this setting, code compatible to previous or newer 
CPU operating system versions in accordance with the 
project requirements may be generated. 
SILworX 
V5 with 
new 
projects 
The code is generated as in SILworX V2. With 
this setting, the use of the code on standard 
devices and modules is supported for CPU 
operating system V7. 
Not applicable for HIMatrix controllers! 
The generated code is compatible to the CPU 
operating system V8. 
Corresponds to SILworX V4. This setting 
ensures the compatibility with future versions.