System Manual Modular Systems  7 Start-Up 
HI 800 191 E Rev. 2.02  Page 69 of 114 
  The Write via MAC dialog box appears. 
6.  Type correct values for the connection parameters and the SRS, and enter the access data 
for a user account with administrator rights valid on the controller. Click Write. 
Connection data and S.R.S are configured and it is now possible to log in. 
For further details, refer to the SILworX manual First Steps (HI 801 103 E). 
7.3.8  Loading a Resource Configuration after a Reset 
If the compact system is switched on with engaged reset key, it restarts and resets the 
connections parameters and user account to the default values (only in case of a controller). 
After a new restart with disengaged reset key, the original values are used. 
If the connection parameters were modified in the user program, they can be configured in the 
compact systems such as described in Chapter 7.3.7. 
Logging in as Default User 
After configuring the connection parameters and prior to loading the user program, the default 
user (administrator with empty password) must be used in the following cases: 
  The password for the user account is no longer known. 
  A new user account should be used in the project. 
To log in as default user 
1.  Select the resource in the structure tree. 
2.  Click the Online button located on the Action Bar or select Online on the context menu. 
  The System Login dialog box appears. 
3.  In the IP Address field, select the correct address or use the MAC address. 
4.  Enter Administrator in the User Group field. 
5.  Let the Password field empty or cancel the password. 
6.  Select Administrator in the Access Mode field. 
7.  Click Log-in. 
SILworX is connected to the HIMatrix controller with default user rights. 
Use <Ctrl>+A in the System Login dialog box to skip steps 4-6! 
7.3.9  Loading a Resource Configuration from the PADT 
Before a user program can be loaded with the connection parameters (IP address, subnet mask 
and system ID) into the controller, the code must have been generated for the resource, and the 
connection parameters for PADT and resource must be valid, see Chapter 7.3.7. 
To load a resource configuration from the PADT 
1.  Select a resource in the structure tree. 
2.  Click the Online button located on the Action Bar or select Online on the context menu. 
3.  In the System Login dialog box, enter a user group with administrator rights or write access. 
  The Control Panel appears in the workspace and displays the controller state. 
4.  In the Online menu, select Resource Download. 
  The Resource Download dialog box appears. 
5.  Click OK to confirm the download. 
  SILworX loads the configuration into the controller. 
6.  Upon completion of the loading procedure, click the Resource Cold Start function on the 
Online menu to start the user program. 
  After the cold start, System State and Program Status enter the RUN state. 
The resource configuration is loaded from the PADT. 
The Start, Stop and Load functions are also available as symbols on the Symbol Bar.