System Manual Modular Systems 7 Start-Up
HI 800 191 E Rev. 2.02 Page 55 of 114
7.3.1.1 Resource Properties
The system parameters of the resource determine the controller behavior during operation and
can be set in SILworX, in the Properties dialog box of the resource.
Parameter
Description
Default
value
Setting for safe
operation
Name
Resource name
Arbitrary
System ID [SRS]
System ID of the resource
1...65 535
The value assigned to the system ID must differ to the
default value, otherwise the project is not able to run!
60 000
Unique value
within the
controller
network. This
network
includes all
controllers that
can potentially
be
interconnected
Safety Time [ms]
Safety time in milliseconds
20...22 500 ms
600 ms/
400 ms
1)
Application-
specific
Watchdog Time
[ms]
Watchdog time in milliseconds: 4...5000 ms for F*03
devices and modules; 8…5000 ms for standard devices
and modules
200 ms/
100 ms
1)
Application-
specific
Target Cycle
Time [ms]
Targeted or maximum cycle time, see Target Cycle Time
Mode, 0...7500 ms. The maximum target cycle time value
may not exceed the watchdog time - minimum watchdog
time; otherwise it is rejected by the PES.
If the default value 0 ms is set, the target cycle time is not
taken into account.
0 ms
Application-
specific
Target Cycle
Time Mode
Use of Target Cycle Time [ms] see Table 27.
With F*03 devices/modules, all the values can be used;
with standard devices/modules, only fixed values!
Fixed-
tolerant
Application-
specific
Multitasking Mode
Only applicable with F*03 devices/modules!
Mode 1
Application-
specific
Mode 1
The duration of a CPU cycle is based on the
required execution time of all user programs.
Mode 2
The processor provides user programs with a
higher priority the execution time not needed by
user programs with a lower priority. Operation
mode for high availability.
Mode 3
During the execution time not needed by the
user programs, the processor waits for the time
to expire, thus increasing the cycle.
Max.Com. Time
Slice ASYNC [ms]
Highest value in ms for the time slice used for
communication during a resource cycle, see the
communication manual (HI 801 101 E),
2...5000 ms
60 ms
Application-
specific
Max. Duration of
Configuration
Connections [ms]
Only applicable with F*03 devices/modules!
It defines how much time within a CPU cycle is available
for process data communication, 2...3500 ms
6 ms
Application-
specific
Maximum System
Bus Latency [µs]
Not applicable for HIMatrix controllers!
0 µs
-