7 Start-Up System Manual Modular Systems
Page 62 of 114 HI 800 191 E Rev. 2.02
7.3.1.5 Rack System Parameter Settings
The rack system parameters can be set in the Rack's online view.
Parameter
Description
Default
value
Type
Spare, not changeable
-
Name
Rack name for the controller, text
HIMatrix
F...Rack
Rack ID
Not changeable
0
Temperature Monitoring
With F*03 devices only!
Specifies the temperature threshold that, if exceeded, causes a
warning message to be created:
Warning at temperature thresholds 1 and 2
Warning at temperature threshold 2 only
Warning at temperature threshold 1 only
No warning at temperature thresholds 1 and 2
Warning at
temperature
thresholds 1
and 2
Table 31: System Parameters of the Rack
7.3.2 Configuring the Ethernet Interfaces
Ethernet interfaces are configured in the Detail View of the communication module. If the
remote I/Os have no communication module, the Ethernet interfaces are configured in the Detail
View of the processor module. Refer to the manuals of the HIMatrix controllers and remote I/Os
for more details.
7.3.3 Configuring the User Program
The following user program switches and parameters can be set in the Properties dialog box of
the user program:
Switch /
Parameter
Function
Default
value
Setting for
safe operation
Name
Name of the user program
Arbitrary
Program ID
ID for identifying the program when displayed in SILworX,
0…4 294 967 295.
If Code Generation Compatibility is set to SILworX V2,
only the value 1 is permitted. (These settings are required
for standard devices and modules).
0
Application-
specific
Priority
Only applicable with F*03!
Priority of the user program: 0...31, if multitasking is used
0
Application-
specific
Program's
Maximum Number
of CPU Cycles
Maximum number of CPU cycles that a user program
cycle may encompass.
A value greater than 1 is only allowed for HIMatrix
controllers F*03!
1
Application-
specific
Max. Duration for
Each Cycle [µs]
Maximum time in each processor module cycle for
executing the user program: 1...4 294 967 295 µs.
Set to 0: No limitation.
A value other than 0 µs is only allowed for HIMatrix
controllers F*03!
0 µs
0 µs
Watchdog Time
[ms] (calculated)
Monitoring time of the user program, calculated from the
Program's Maximum Number of Cycles and the watchdog
time of the resource
Not changeable!
-
i
For HIMatrix F*03 systems with counter inputs,
ensure that the user program's watchdog time is
less than or equal to 5000 ms.