7 Start-Up System Manual Modular Systems
Page 68 of 114 HI 800 191 E Rev. 2.02
The following table shows the connection of the system variables in the input module's Detail
View to global variables:
-> Value [BOOL] of the corresponding
channel
S1_1_Pulsed…S2_2_Pulsed (one variable for each
channel)
-> Error Code [BYTE] of the
corresponding channel
FC_S1_1_Pulsed…FC_S2_2_Pulsed (one variable
for each channel)
Table 38: Connection of the Global Variables to Input System Variables of the Input Module
Activation of Pulsed Outputs
From the DOxx: Channels tab located in the output module's Detail View, connect the Value
[BOOL] -> system variable of every fourth successive channels (=Sum_Pulse) with Pulse_ON.
The logical value of the Pulse_ON variable is TRUE. This results in pulsed outputs that are
permanently activated and only set to FALSE for the duration of the pulse actuation.
7.3.6 Generating the Resource Configuration
With the following procedure, the code is generated twice and the resulting CRCs are compared
with one another.
To generate the code for the resource configuration
1. Select the resource in the structure tree.
2. Click the Code Generation button located on the Action Bar or select Code Generation on
the context menu.
The Code Generation <Resource Name> dialog box appears.
3. Select CRC Comparison on the Code Generation <Resource Name> dialog box (default
value).
4. In the Start Code Generation dialog box, click OK.
An additional Start Code Generation appears, shows the progress of the two code
generation processes and is closed again. The logbook contains one row informing about
the code generation result and one row reporting the result of the CRC comparison.
A valid code is generated for the resource configuration.
Failures during the code generation may occur due to the non-safe PC!
For safety-related applications, the code generator must generate the code two times
and the checksums (CRCs) resulting from the two code generations must be identical.
Only if this is the case, an error-free code is ensured.
Refer to the safety manual (HI 800 023 E) for further details.
7.3.7 Configuring the System ID and the Connection Parameters
To configuring the system ID and the connection parameters
1. Select the resource in the structure tree.
2. Click the Online button located on the Action Bar or select Online on the context menu.
The System Login dialog box appears.
3. Click Search.
The Search per MAC dialog box appears.
4. Enter the MAC address valid for the controller - see the label on the housing - and click
Search.
In the dialog box, the values set for IP address, subnet mask and S.R.S are displayed.