System Manual Modular Systems 7 Start-Up
HI 800 191 E Rev. 2.02 Page 59 of 114
After starting the controller, no operating action
such as stop, start or download is permitted in
SILworX , except for forcing and reload.
Relay Contact 1
...Relay Contact 4
Only applicable with F60!
It controls the corresponding relay contacts, if
existing.
Only applicable with F*03!
It prevents the controller from being by performing
a reload.
Only applicable with F*03!
It controls the corresponding LED, if existing.
Table 29: Hardware System Variables - CPU OS V7 and Higher
Global variables can be connected to these system variables; the value of the global variables is
modified using a physical input or the user program logic.
7.3.1.4 Hardware System Variables for Reading the Parameters
These system variables can be accessed in the SILworX Hardware Editor.
Select the gray background outside the (yellow) subrack representation and double-click or use
the context menu to open the Detail View.
Number of current I/O errors
Number of Field Errors -
Historic Count
Counted number of I/O errors (counter resettable)
Number of current I/O warnings
Number of Field Warnings -
Historic Count
Counted number of I/O warnings (counter resettable)
Communication Error Count
Number of current communication errors
Communication Error Historic
Count
Counted number of communication errors (counter resettable)
Communication Warning
Count
Number of current communication warnings
Communication Warnings
Historic Count
Counted number of communication warnings (counter resettable)
Number of current system errors
System Error Historic Count
Counted number of system errors (counter resettable)
Number of current system warnings
System Warning Historic
Count
Counted number of system warnings (counter resettable)
When the processor system is connected to the supply
voltage, it automatically starts the user program
When the processor system is connected to the supply
voltage, it enters the STOP state
Operating system version contained in processor system
Resource configuration checksum
System date and time in s and ms since 1970-01-01