7 Start-Up System Manual Modular Systems
Page 66 of 114 HI 800 191 E Rev. 2.02
Module slot with pulsed
outputs
With compact devices, the
DOs are used in slot 1, 2 or
3, see Table 35.
With the F60, the slot (3...8)
is given.
Value in µs
Maximum value: 2000 µs
F20: Pulse delay must be ≥
500 µs.
Refer to the F20 manual.
Pulse 1
Pulse 2
...
Pulse 8
Pulse 1...8, as required, must
match the number of pulsed
outputs.
Initialization value for
pulsed outputs
Activation of pulsed outputs
Table 33: Parameters for Line Control
The signal can be named freely; the names used in this manual are examples. All parameters
have the Const attribute.
The following table specifies the switch variables used in the example:
First and second contact of
switch 1
First and second contact of
switch 2
FC_S1_1_pulsed
FC_S1_2_pulsed
Error codes for first and second
contact of switch 1
FC_S2_1_pulsed
FC_S2_2_pulsed
Error codes for first and second
contact of switch 2
Table 34: Switch Variables for Line Control
The following table specifies the slot numbers of modules with pulsed outputs when compact
devices are used.
DI Pulse Slot system parameter
Table 35: Module Slot with Pulsed Outputs
If the modular F60 system is used, the number of the slot in which the module with pulsed
outputs is inserted, must be used (3…8).
7.3.5.2 Configuring Pulsed Outputs
The pulsed outputs must begin in SILworX with channel 1 and reside in direct sequence, one
after the other.