System Manual Modular Systems 7 Start-Up
HI 800 191 E Rev. 2.02 Page 79 of 114
Parameter
Range
Description
Default value
Off:
Load not allowed
Test Mode
Allowed
On/Off
Test Mode
Off
On:
Test Mode Allowed
Off:
Test mode not allowed
Changing the
variables in the
OLT allowed
On/Off
Changing variables in the online test
On
On:
Allowed
Off:
Not Allowed
Forcing Allowed
On/Off
On:
Forcing Allowed
Off
Off:
Forcing not allowed
Stop at Force
Timeout
On/Off
On:
STOP upon expiration of the force
time.
On
Off:
No STOP upon expiration of the force
time.
Max. Com.Time
Slice [ms]
2...5 000 ms
Time for performing the communication
tasks
10 ms
Table 44: Resource Configuration Parameters - CPU OS up to V7
Refer to the HIMatrix system safety manual (HI 800 023 E) for more details on how to configure
a resource for safety-related operation.
7.7.2 Configuring the User Program
General system signals and parameters