System Manual Modular Systems 7 Start-Up
HI 800 191 E Rev. 2.02 Page 63 of 114
Switch /
Parameter
Function
Default
value
Setting for
safe operation
Classification
Classification of the user program: Safety-related or
Standard (for documentation only).
Safety-
related
Application-
specific
Allow Online
Settings
It enables changes of other user program switches during
operation.
It only applies if the Allowed Online Settings switch for the
resource is set to ON!
ON
-
Autostart
Enabled type of Autostart: Cold Start, Warm Start, Off
Warm
start
Application-
specific
Start Allowed
ON:
The PADT may be used to start the user program.
ON
Application-
specific
OFF:
The PADT may not be used to start the user
program
Test Mode Allowed
ON
The test mode is permitted for the user program.
OFF
Application-
specific
OFF
The test mode is not permitted for the user program.
Reload Allowed
ON:
User program reload is permitted
ON
Application-
specific
OFF:
User program reload is not permitted
Local Forcing
Allowed
ON:
Forcing permitted at program level
OFF
OFF is
recommended
OFF:
Forcing not permitted at program level
Local Force
Timeout Reaction
Behavior of the user program after the forcing time has
expired:
Stop Forcing Only.
Stop Program.
Stop
Forcing
Only.
Application-
specific
Code Generation
Compatibility
SILworX V4
Code generation is compatible with
SILworX V4.
SILworX
V4 with
new
projects
SILworX V2 with
CPU OS V7
SILworX V4 with
CPU OS V8
SILworX V3
Not applicable for HIMatrix controllers!
SILworX V2
Code generation is compatible with
SILworX V2.
Table 32: System Parameters of the User Program - CPU OS V7 and Higher
Notes specific to the Code Generation Compatibility Parameter:
In a new project, SILworX selects the latest value for the Code Generation Compatibility
parameter. This ensures that the current, enhanced features are activated and the latest
hardware and operating system versions are supported. Verify that this setting is in
accordance with the hardware in use, e.g., in HIMatrix standard devices, Minimum
Configuration Version must be set to SILworX V2.
In a project converted from a previous SILworX version, the value for Code Generation
Compatibility remains the value set in the previous version. This ensures that the
configuration CRC resulting from the code generation is the same as in the previous version
and the generated configuration is compatible with the operating systems in the hardware.
For this reason, the value of Code Generation Compatibility should not be changed for
converted projects.
If a Minimum Configuration Version of SILworX V4 or higher is set for a resource (see
above), the Code Generation Compatibility parameter must be set to SILworX V4 in every
user program. If SILworX V2 is required, the Minimum Configuration Version resource
parameter must be set to SILworX V2.
7.3.4 Configuring the Inputs and Outputs
In the Hardware Editor, the inputs and outputs are configured by connecting global variables to
the system variables for input and output channels.
To access the system variables for input and output channels
1. Display the desired resource in the Hardware Editor.
2. Double-click the required input or output module to open the corresponding Detail View.