4 Start-up  X-AI 32 01 
Page 36 of 58  HI 801 021 E Rev. 4.00 
4.3.2  Tab: I/O Submodule AI32_01 
The I/O Submodule AI32 01 tab contains the following statuses and parameters: 
Name  R/W  Description 
Enter these statuses and parameters directly in the Hardware Editor. 
Name R Module name 
Supply ON  W  Use the transmitter supplies of the module. 
Activated: Transmitter supplies for channels 1 to 32 
activated. 
Deactivated: Transmitter supplies for channels 1 to 32 
deactivated. 
Default setting: Activated 
Show Signal Overflow  W  The Field LED displays a potential signal overflow. 
Activated: Show signal overflow activated. 
Deactivated: Show signal overflow deactivated 
Default setting: Activated 
Show Supply Overcurrent  W  Show supply overcurrent with Field LED.  
Activated: Show supply overcurrent activated. 
Deactivated: Show supply overcurrent deactivated. 
Default setting: Activated 
Name  Data type  R/W  Description 
The following statuses and parameters can be assigned global variables and used in the user program. 
Diagnostic Request  DINT  W 
To request a diagnostic value, the appropriate ID must be 
sent to the module using the parameter Diagnostic 
Request (see Chapter 
4.3.5 for coding details). 
Diagnostic Response  DINT  R 
As soon as Diagnostic Response returns the ID of 
Diagnostic Request (see 
4.3.5 for coding details), 
Diagnostic Status contains the diagnostic value 
requested. 
Diagnostic Status  DWORD  R 
Requested diagnostic value in accordance with 
Diagnostic Response. 
The IDs of Diagnostic Request and Diagnostic Response 
can be evaluated in the user program. Diagnostic Status 
only contains the requested diagnostic value when both 
Diagnostic Request and Diagnostic Response have the 
same ID. 
Background Test Error  BOOL  R  TRUE: Background test is faulty 
FALSE: Background test is free of faults 
Restart on Error  BOOL  W 
Using the parameter Restart on Error, each I/O module 
that has switched off permanently due to faults can be 
forced to re-adopt the RUN state. To do this, set the 
Restart on Error parameter FALSE to TRUE. 
The I/O module performs a complete self-test and only 
enters the RUN state if no faults are detected. 
Default setting: FALSE 
Submodule OK  BOOL  R  TRUE: No submodule fault. 
No channel faults. 
FALSE: Submodule fault. 
Channel fault (external faults included) 
Submodule Status  DWORD  R  Bit-coded submodule status 
(For coding details, see Chapter 
4.3.4) 
Table 22:  Tab: I/O Submodule AI32_01 in the Hardware Editor