PowerMICE
Release
 
01
 
04/2014
31
 Failure of the redundancy.
 The removal of the AutoConfiguration Adapter.
The following condition is also reported in RM mode:
 Ring redundancy guaranteed. By default, there is no ring redundancy 
monitoring
 Pull the terminal block off the device and connect the voltage supply 
lines and the signal lines.
2.2.9 Installing the terminal blocks; start-up procedure
 Mount the terminal blocks for the voltage supply and the signal contact on 
the bottom of the device using the snap locks.
Make sure the snap lock latches securely in place.
By connecting the voltage supply via the terminal blocks, you start the 
operation of the device.
2.2.10 Installing the device on the DIN rail, grounding
 Mount the device on a 35 mm DIN rail in accordance with DIN EN 60175.
 Attach the upper snap-in guide of the device into the DIN rail and press 
the device down against the DIN rail until it snaps into place.
Note: The shielding ground of the industrial connectable twisted pair lines is 
connected to the lower panel as a conductor.
Figure 13: Assembly
 Grounding
The lower panel of the device housing is grounded by means of the DIN 
rail and optionally by means of the separate ground screw (see fig. 2).