Continuously press “˚” , “˘” of the time setting key ,
and the user may check the set codes and content for
18
Step 5
commonly used items of in-situ settings, see details below:
No. Code
Settings
Default
Value
Range
Minimum
Adjusting
Unit
Unit Explanation to Functions Remarks
1
automatic temperaure
adjustment
inactive inactive/active / / OTC function inactive/active 00 inactive, 01 active
2
beginning time of
automatic
temperature
adjustment
23:00 0:00-23:00 1 h beginning time of OTC
value indicates 24 hours per
day
3
ending time of
automatic
temperature
adjustment
5:00 0:00-23:00 1 h ending time of OTC
value indicates 24 hours per
day
4
low environmental
temperature
-20 -20~5 1 °C
value indicates temperature
range
5
high environmental
temperature
20 6~25 1 °C
value indicates temperature
range
6
set water temperature
of low environmental
temperature
44 20~55 1 °C
value indicates temperature
range
7
set water temperature
of high environmental
temperature
25 25~55 1 °C
determine the OTC temperature curve
value indicates temperature
range
8
sterilization selection inactive inactive/active / / sterilization inactive/active 00 inactive
,
01active
9
sterilization run time 0:00 0:00-23:00 1 h beginning time of sterilization
value indicates 24 hours per
day
10
sterilization run date 06 01~07 1 day default run time is each Saturday
value indicates 7 days per
week
11
sterilization lasting
time
10 10~60 1 min sterilization lasting time
value indicates range of
minutes
12
sterilization
temperature setting
70 50~70 1 °C sterilization temperature
value indicates temperature
range
13
electric heating of
water module
active active/inactive / /
electric heating of water module
active/inactive
00 inactive, 01 active
14
domestic hot water
(water tank mode)
inactive inactive/active / / water tank mode inactive/active 00 inactive, 01 active
15
floor heating active active/inactive / / floor heating active/inactive 00 inactive, 01 active
16
electric heating of
water tank
inactive inactive/active / / 00 inactive, 01 active
17
electric heating work
mode of water tank
ordinary ordinary/advanced / /
Advanced mode will increase frequency
of using electric heating of water tank
and accelerate water heating speed, but
this will increase electricity
consumption.
00 inactive, 01 active
18
water tank lowest
water temperature
guarantee during floor
heating
inactive inactive/active / /
After the setting is active, during floor
heating, start the electric heating of
water tank and ensure that the water
tank is not lower than the temperature
set by F5.
00 inactive, 01 active
19
heat recovery inactive inactive/active / /
When the domestic water tank is
installed and the function is active,
during air conditioner cooling, water
module can conduct heat recovery
running.
00 inactive, 01 active
20
starting outdoor
environmental
temperature of
electric heating of
water module
4 -20~10 1 °C
the outdoor environmental temperature
is higher than the set value, and electric
heating of water module can’t start.
value indicates temperature
range
21
lowest water
temperature
guarantee of water
tank during standby
inactive inactive/active / /
After the setting is active, the wire
controller at off state can start the
electric heating of water tank to keep the
water tank is not lower than the
temperature set by F5.
00 inactive, 01 active
22
lowest water
temperature
guarantee of water
tank
35 35~65 1 °C
When the lowest water temperature
guarantee of water tank is active, the
water tank temperature is lower than the
set value, and start the electric heating
to guarantee the water tank
temperature.
value indicates temperature
range
23
water temperature set
value of powerful
water storage
45 35~75 1 °C
After power water storage is running
and reaches the “water tank storage
water temperature”, system quits.
value indicates temperature
range
24
forced run of water
pump
inactive inactive/active / /
During commissioning, forced start the
water pump for water pipe vents, or else
the air in the circulating pipe can’t be
vented. After commissioning, set it as
inactive again, or else the water pump
will continuously run.
00 inactive, 01 active
11