L200 Inverter
Operations
and Monitoring
4–19
Free-run Stop
When the terminal [FRS] is turned ON, the inverter stops the output and the motor enters
the free-run state (coasting). If terminal [FRS] is turned OFF, the output resumes sending
power to the motor if the Run command is still active. The free-run stop feature works
with other parameters to provide flexibility in stopping and starting motor rotation.
In the figure below, parameter B088 selects whether the inverter resumes operation from
0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS]
terminal turns OFF. The application determines the best setting.
Parameter B003 specifies a delay time before resuming operation from a free-run stop.
To disable this feature, use a zero delay time.
Motor
speed
[FW],
[RV]
Zero-frequency start
Motor
speed
Resume from motor speed
wait time
B088
=
00 B088
=
01
1
0
tt
FRS FRS
[FW],
[RV]
1
0
1
0
1
0
B003
Option
Code
Terminal
Symbol
Function Name
Input
State
Description
11 FRS Free-run Stop ON Causes output to turn OFF, allowing motor to
free run (coast) to stop
OFF Output operates normally, so controlled deceler-
ation stops motor
Valid for inputs:
C001, C002, C003, C004,
C005
Required settings:
B003, B088, C011 to C015
Notes:
When you want the [FRS] terminal to be active low
(normally closed logic), change the setting (C011
to C015) that corresponds to the input (C001 to
C005) that is assigned the [FRS] function.
Example (requires input configuration—
see page 3–42
):
See I/O specs on page 4–6
.
FRS
12345L
PCS