ModBus Data Listing
Appendix B
B–34
B084 Initialization mode
(parameters or trip
history)
R/W Select the type of initialization
to occur, two option codes:
00...Trip history clear
01...Parameter initialization
02...Trip history clear and
parameter initialization
009Ah 0, 1, 2
B085 Country code for initial-
ization (not accessible
to ModBus)
Select default parameter values
for country on initialization.
Note: Write not allowed from
network.
009Bh
B086 Frequency scaling
conversion factor
R/W Specify a constant to scale the
displayed frequency for D007
monitor, range is 0.1 to 99.9
009Ch 1 to 999 0.1
B087 STOP key enable R/W Select whether the STOP key
on the keypad is enabled, two
option codes:
00...enabled
01...disabled
009Dh 0, 1
B088 Restart mode after FRS R/W Selects how the inverter
resumes operation when the
free-run stop (FRS) is
cancelled, two options:
00...Restart from 0Hz
01...Restart from frequency
detected from real speed of
motor (frequency matching)
009Eh 0, 1
B089 Monitor display select
for networked inverter
R/W Selects the parameter
displayed on the keypad
display when the inverter is
networked, 7 options:
01...Output frequency monitor
02...Output current monitor
03...Rotation direction
monitor
04...Process variable (PV),
PID feedback monitor
05...Intelligent input terminal
status
06...Intelligent output terminal
status
07...Scaled output frequency
monitor
00E9h 1 to 7
B091 Stop mode selection R/W Selects how the inverter stops
the motor, two option codes:
00...DEC (decelerate and stop)
01...FRS (free run to stop)
00A0h 0, 1
“B” Group Fine Tuning Functions
Func.
Code
Name R/W Description
Network Data
Reg. Range Res.