¿ Branch pipe (PDF 23C3, PDF 46C3)
If there are obstacles such as partitions inside the room that prevent
the air from circulating correctly, branches can be installed to
provide an even air temperature.
Suitable return air grilles must be installed in line with the volume
of return air. If air conditioning is provided in an adjoining room,
always install a return grille.
Example of a branch pipe.
Branch pipe installation
The connections for the branch pipe are indicated in the following
figure.
There are six knockout holes. Cut the insulation material on the
outer surface in a circle and line up the notches at the four corners.
Use a screwdriver or similar and remove.
Prepare the square connection duct (field-supplied) or use a
flexible duct with a diameter of 150 or 200 mm.
Duct connection dimensions
Model
Units a b c d
PDF-23C3 RCI-(1.5-2.5)FSN2E 150 155 9 248
PDF-46C3 RCI-(3.0-6.0)FSN2E 200 180 6 298
Fit enough insulation to the connection between the pipe and the main body of the indoor unit and to the connection between
the duct and the pipe.
2 Unit installation
71
SMGB0063 rev. 1 - 10/2010
2