4.2.42 Jogging (JG) command setting
The jogging command setting function allows you to set and finely tune
the motor-stopping position.
To use this function, assign function "06" (JG) to an intelligent input
terminal.
(1) Jog frequency setting
Since the inverter operates the motor with a full voltage for the jogging operation, the inverter can easily trip during
the latter. Adjust the jog frequency setting (A038) properly so that the inverter will not trip.
0.0 or "start frequency" to
9.99 (Hz)
Setting of the frequency to output during jogging
operation
(2) Jog stop mode
Disabling jogging while the motor is operating and
enabling free-running when the motor is stopped
Disabling jogging while the motor is operating and
enabling stopping after deceleration when the motor
is stopped
Disabling jogging while the motor is operating and
enabling DC braking when the motor is stopped
Enabling jogging while the motor is operating and
enabling free-running when the motor is stopped
Enabling jogging while the motor is operating and
enabling stopping after deceleration when the motor
is stopped
Enabling jogging while the motor is operating and
enabling DC braking when the motor is stopped
Note 1: To perform the jogging operation, always turn on the JG terminal before turning on the FW or RV terminals.
(Follow this sequence of command inputs also when using the digital operator to enter operation commands.)
(Example 1) (Example 2)
Note 2: You must set DC braking data if you specify "02" or "05" for the jog stop mode (A039). (See Section 4.2.19.)
A038: Jog frequency setting
A039: Jog stop mode
C001 to C008: Terminal [1] to [8] functions
When "00", "01", or "02" is specified for the jog stop
mode (A039), the jogging operation will not be
performed if the FW signal is turned on earlier than the
JG signal.
When "03", "04", or "05" is specified for the jog stop mode (A039),
the jogging operation will be performed, even if the FW signal is
turned on earlier than the JG signal. However, the motor will stop
after free-running if the JG signal is turned off earlier than the FW
signal.
Acceleration according to the setting of "b088"