Chapter 4 Explanation of Functions
4-113
4.4 Communication Functions
The inverter can engage in RS485 communications with an external
control system that is connected to the TM2 terminal block (on the
control circuit terminal block board) of the inverter.
The SJ700 series inverter shares the ASCII communication protocol
with the SJ300 and L300P series inverters.
(1) Communication specifications
2,400, 4,800, 9,600, or 19,200 bps
Selection with the digital operator
Half-duplex communication
Asynchronous
transmission
Transmission beginning with the lowest-order bit
Selection with the digital operator
No parity, even parity, or odd parity
Selection with the digital operator
Selection with the digital operator
Initiation only by a command from the external control
system
Setting with the digital operator
1-to-N connection (N: Maximum of 32 [inverters])
Station number to be selected with
the digital operator
Overrun, framing, BCC,
vertical parity, and
longitudinal parity errors
Overrun, framing, CRC-16,
and longitudinal parity
errors
<Specifications and connections of RS485 ports>
For the RS485 communication function, use the TM2 terminal block on the control circuit terminal block board.
Abbreviated
name of
terminal
Positive signal terminal for
transmission
Negative signal terminal
for transmission
Terminal to enable the
terminating resistor
Terminal to enable the
terminating resistor
Followings are recommended as the wire to connect TM2.
Solid-core wire 0.14mm
2
-1.5mm
2
(when two wires are on one terminal pole,0.14 mm
2
-0.5mm
2
)
Standard wire 0.14mm
2
-1.0mm
2
(when two wires are on one terminal pole,0.14 mm
2
-0.2mm
2
)
Standard wire with bar terminal 0.25mm
2
-0.5mm
2
Striped covering length 5mm
Screw torque 0.22Nm-0.25Nm(screw size M2)
A001: Frequency source setting
A002: Run command source setting
C071: Communication speed selection
C072: Node allocation
C073: Communication data length selection
C074: Communication parity selection
C075: Communication stop bit selection
C078: Communication wait time
C079: Communication mode selection