Chapter 4 Explanation of Functions
4-60
4.2.58 Intelligent output terminal setting
You can assign the functions described below to the intelligent output
terminals [11] to [15] (C021 to C025) and the alarm relay terminal
(C026).
The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal is used
for relay output.
You can select the a-contact or b-contact output for individual output terminals by using functions "C031" to "C035"
and "C036".
When "01" (3 bits) or "02" (4 bits) is specified for the alarm code output "C062" (see Section 4.2.65), the alarm code
output is assigned to output terminals 11 to 13 or output terminals 11 to 14 (AC0 to AC3), respectively. Subsequently,
the settings of "C021" to "C024" are invalidated.
FA1: Constant-speed reached
Frequency-arrival signals
FA2: Set frequency overreached
OL: Overload notice advance signal (1)
Overload restriction/overload notice advance signal
OD: Output deviation for PID control
FA3: Set frequency reached
Frequency-arrival signals
IP: Instantaneous power failure
Instantaneous power failure/undervoltage
Torque limitation function
Operation time over signal
THM: Thermal alarm signal
Electronic thermal protection
ZS: 0 Hz detection signal
DSE: Speed deviation maximum
V2 control mode selection function
POK: Positioning completed
FA4: Set frequency overreached 2
Frequency-arrival signals
FA5: Set frequency reached 2
OL2: Overload notice advance signal (2)
Overload restriction/overload notice advance signal
Odc: Analog O disconnection detection
Window comparators function
OIDc: Analog OI disconnection detection
O2Dc: Analog O2 disconnection detection
FBV: PID feedback comparison
NDc: Communication line disconnection
LOG1: Logical operation result 1
Logical operation function
LOG2: Logical operation result 2
LOG3: Logical operation result 3
LOG4: Logical operation result 4
LOG5: Logical operation result 5
LOG6: Logical operation result 6
WAC: Capacitor life warning
WAF: Cooling-fan speed drop
FR: Starting contact signal
OHF: Heat sink overheat warning
Heat sink overheat warning
LOC: Low-current indication signal
Low-current indication signal
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function