Chapter 8 List of Data Settings
8-1
FW
8
7
6
5
4
3
2
1
AL
15
14
13
12
11
IMPORTANT! Please be sure to set the motor nameplate data into appropriate parameters to ensure proper
operation and protection of the motor.
*b012 is the motor overload protection value
*A082 is the motor voltage selection
*H003 is the motor kW capacity
*H004 is the number of motor poles
Please refer to the appropriate pages in this guide and the Instruction Manual for further details.
8.1 Precautions for Data Setting
- FF, FEF and FUF are the parts of inverter model.
For example, in case of 1.5kW/400V class, SJ700D-015H***3 (*** is described as FF, FEF or FUF.)
- Even though the inverter is driving the motor, you can change some parameters. If you specify "10" for the
software lock mode selection (b031), you can change some more parameters. See the table below.
8.2 Monitoring Mode
With the default settings, the initial display on the operator after powering on is always the output frequency
monitor (d001). To change the initial display content, change the setting of the initial-screen selection (b038) as
required.
Code
Function name
Monitored data or setting
Default
Change during
RUN operation
Page
FF
FEF
FUF
b03110
b031=10
d001
Output frequency monitoring
0.00 to 99.99, 100.0 to 400.0 (Hz)
Allowed
Allowed
4-1
d002
Output current monitoring
0.0 to 999.9, 1000 to 9999 (A)
4-1
d003
Rotation direction minitoring
F (forward rotation), o (stopped), r (reverse rotation)
4-1
d004
Process variable (PV),
PID feedback monitoring
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)
4-1
d005
Intelligent input
terminal status
(Example)
Terminals FW, 7, 2, and 1: ON
Terminals 8, 6, 5, 4, and 3: OFF
4-2
d006
Intelligent output
terminal status
(Example)
Terminals 12 and 11: ON
Terminals AL, 15, 14, and 13: OFF
4-2
d007
Scaled output frequency
monitoring
0.00 to 99.99, 100.0 to 999.9, 1000. to 9999., 1000 to 3996 (10000 to 39960)
Allowed
Allowed
4-2
d008
Actual-frequency monitoring
-400. to -100., -99.9 to 0.00 to 99.99, 100.0 to 400.0 (Hz)
4-3
d009
Torque command monitoring
-200. to +200. (%)
4-3
d010
Torque bias monitoring
4-3
d012
Torque monitoring
4-3
d013
Output voltage monitoring
0.0 to 600.0 (V)
4-3
d014
Power monitoring
0.0 to 999.9 (kW)
4-3
d015
Cumulative power monitoring
0.0 to 999.9, 1000. to 9999.
1000 to 9999 (10000 to 99990), 100 to 999 (100000 to 999000)
4-4
d016
Cumulative operation RUN time
monitoring
0. to 9999., 1000 to 9999 (10000 to 99990),
100 to 999 (100000 to 999000) (hr)
4-4
d017
Cumulative power-on time
monitoring
4-4
d018
Heat sink temperature monitoring
-020. to 200.0 (C)
4-4
d019
Motor temperature monitoring
4-4